Rehabilitation of a DN 400 GRP irrigation pipe under the main road towards Palm JumeirahRehabilitation of a DN 400 GRP irrigation pipe under the main road towards Palm JumeirahRehabilitation of a DN 400 GRP irrigation pipe under the main road towards Palm JumeirahRehabilitation of a DN 400 GRP irrigation pipe under the main road towards Palm Jumeirah
  • Home
  • About
  • Services
    • Trenchless Pipe Repair and Rehabilitation
    • Spoolable Composite Pipe Installation
    • Turn-key Pipe Repair & Installation Solutions
  • Products
    • Primusline
    • Baker Hughes
  • References
  • News
  • Contact
✕
Rehabilitation of a DN 400 potable water main underneath a bridge in Istanbul
Mayıs 5, 2022
Renovation of a Sewer Rising Main at Heathrow Airport
Mayıs 5, 2022
Rehabilitation of a DN 400 GRP irrigation pipe under the main road towards Palm Jumeirah

Client:
Dubai Municipality

Year of Construction:
May 2019

Situation:
An existing GRP DN 400 irrigation pipe was leaking due to soil settling. This water main is crossing one of the major roads towards the Palm Jumeirah road in Dubai with two 45 degree bends. Traditional open trench excavation was not feasible. Moreover, the water main is only accessible via small maintenance chambers – one located directly in the road, the other at an adjacent parking lot. The fittings in the chambers were removed and the host pipe was cut flush with the wall of the chamber to create the necessary working space. After cleaning the host pipe, a CCTV inspection was performed. The pre-folded DN 400 Primus Liner was inserted in 15 minutes and re-rounded. Due to the confined space situation, the connectors were specifically produced for this project and equipped with a wall-mounting plate to fix to the chamber’s wall. A hydrostatic pressure test was suc-cessfully performed after the renovation works. The entire rehabilitation was com-pleted in two night shifts.

Technical Details:
Transported Fluid: Irrigation water
Diameter of Host Pipe: DN 400
Material of Host Pipe: GRP
Operating Pressure: 6 bar
Primus Line® System: DN 400 PN 18
Total Length: 140 m in one section
Bends: Two 45-degree bends
Number of Sections: One section

Case Study
Share

Related posts

Mayıs 5, 2022

Rehabilitation of a DN 200/DN 300 water pipe in Split


Read more
Mayıs 5, 2022

Renovating 1.5 km of DN 500 asbestos cement water main in 60 hours


Read more
Mayıs 5, 2022

Rehabilitation of a DN 400 potable water main underneath a bridge in Istanbul


Read more

Cevizli mah. Bağdat cad.
Ethem Güral İş Mrkz.No:515/3
Maltepe/İstanbul

+90 216 370 93 42
info@floramuhendislik.com